Siemens SINAMICS G150 Manual page 1387

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Remedy:
Not necessary.
The message is withdrawn when exiting the acceptance test mode.
Note:
SI: Safety Integrated
SLP: Safely-Limited Position / SE: Safe software limit switches
F01800
DRIVE-CLiQ: Hardware/configuration error
Message value:
%1
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
All objects
Reaction:
Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Infeed: NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A DRIVE-CLiQ connection fault has occurred.
Fault value (r0949, interpret decimal):
100 ... 107:
Communication via DRIVE-CLiQ socket X100 ... X107 has not been switched to cyclic operation. The cause may be
an incorrect structure or a configuration that results in an impossible bus timing.
10:
Loss of the DRIVE-CLiQ connection. The cause may be, for example, that the DRIVE-CLiQ cable was withdrawn
from the Control Unit or as a result of a short-circuit for motors with DRIVE-CLiQ. This fault can only be
acknowledged in cyclic communication.
11:
Repeated faults when detecting the connection. This fault can only be acknowledged in cyclic communication.
12:
A connection was detected but the node ID exchange mechanism does not function. The reason is probably that the
component is defective. This fault can only be acknowledged in cyclic communication.
Remedy:
Re fault value = 100 ... 107:
- ensure that the DRIVE-CLiQ components have the same firmware versions.
- avoid longer topologies for short current controller clock cycles.
For fault value = 10:
- check the DRIVE-CLiQ cables at the Control Unit.
- remove any short-circuit for motors with DRIVE-CLiQ.
- carry out a POWER ON.
For fault value = 11:
- check the electrical cabinet design and cable routing for EMC compliance
For fault value = 12:
- replace the component involved.
A01839
DRIVE-CLiQ diagnostics: cable fault to the component
Message value:
Component number: %1
Message class:
General drive fault (19)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The fault counter (r9936[0...199]) to monitor the DRIVE-CLiQ connections/cables has been incremented.
Alarm value (r2124, interpret decimal):
Component number.
Note:
The component number specifies the component whose feeder cable from the direction of the Control Unit is faulted.
The alarm automatically disappears after 5 seconds, assuming that no other data transfer error has occurred.
See also: r9936 (DRIVE-CLiQ diagnostic error counter connection)
Remedy:
- check the corresponding DRIVE-CLiQ cables.
- check the electrical cabinet design and cable routing for EMC compliance
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1387

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130