F01012 (N)
Project conversion error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
VECTOR_G
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
When converting the project of an older firmware version, an error occurred.
Fault value (r0949, interpret decimal):
Parameter number of the parameter causing the error.
For fault value = 600, the following applies:
The temperature evaluation is no longer assigned to the power unit but to the encoder evaluation.
Notice:
Monitoring of the motor temperature is no longer ensured.
Remedy:
Check the parameter indicated in the fault value and correctly adjust it accordingly.
For fault value = 600:
Parameter p0600 must be set to the values 1, 2 or 3 in accordance with the assignment of the internal encoder
evaluation to the encoder interface.
Value 1 means: The internal encoder evaluation is assigned to the encoder interface 1 via p0187.
Value 2 means: The internal encoder evaluation is assigned to the encoder interface 2 via p0188.
Value 3 means: The internal encoder evaluation is assigned to the encoder interface 3 via p0189.
- If necessary, the internal encoder evaluation must be assigned to an encoder interface via parameters p0187,
p0188 or p0189 accordingly.
- If necessary, upgrade the firmware to a later version.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F01015
Internal software error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
A01016 (F)
Firmware changed
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one firmware file in the directory was illegally changed on the non-volatile memory (memory card/device
memory) with respect to the version when shipped from the factory.
Alarm value (r2124, interpret decimal):
0: Checksum of one file is incorrect.
1: File missing.
2: Too many files.
3: Incorrect firmware version.
4: Incorrect checksum of the back-up file.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms