APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 32 of 48)
ADDR
REGISTER NAME
FlexElement Actuals (Read Only) (16 modules)
9A01
FlexElement™ 1 Actual
9A03
FlexElement™ 2 Actual
9A05
FlexElement™ 3 Actual
9A07
FlexElement™ 4 Actual
9A09
FlexElement™ 5 Actual
9A0B
FlexElement™ 6 Actual
9A0D
FlexElement™ 7 Actual
9A0F
FlexElement™ 8 Actual
Teleprotection Inputs/Outputs (Read/Write Settings)
9B00
Teleprotection Function
9B01
Teleprotection Number of Terminals
9B02
Teleprotection Number of Channels
9B03
Teleprotection Local Relay ID
9B04
Teleprotection Terminal 1 ID
9B05
Teleprotection Terminal 2 ID
9B06
Reserved (10 items)
9B10
Teleprotection Input 1-n Default States (16 items)
9B30
Teleprotection Input 2-n Default States (16 items)
9B50
Teleprotection Output 1-n Operand (16 items)
9B70
Teleprotection Output 2-n Operand (16 items)
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9B90
Teleprotection Clear Lost Packets
Teleprotection Channel Tests (Read Only)
9B91
Teleprotection Channel 1 Status
9B92
Teleprotection Channel 1 Number of Lost Packets
9B93
Teleprotection Channel 2 Status
9B94
Teleprotection Channel 2 Number of Lost Packets
9B95
Teleprotection Network Status
9BA0
Teleprotection Channel 1 Input States
9BA1
Teleprotection Channel 2 Input States
9BB0
Teleprotection Input 1 States, 1 per register (16 items)
9BC0
Teleprotection Input 2 States, 1 per register (16 items)
VT Fuse Failure (Read/Write Setting) (6 modules)
A040
VT Fuse Failure Function
A041
...Repeated for module number 2
A042
...Repeated for module number 3
A043
...Repeated for module number 4
A044
...Repeated for module number 5
A045
...Repeated for module number 6
Selector Switch Actuals (Read Only)
A400
Selector 1 Position
A401
Selector 2 Position
Selector Switch (Read/Write Setting) (2 modules)
A410
Selector 1 Function
A411
Selector 1 Range
A412
Selector 1 Timeout
A413
Selector 1 Step Up
A414
Selector 1 Step Mode
A415
Selector 1 Acknowledge
A416
Selector 1 Bit0
A417
Selector 1 Bit1
A418
Selector 1 Bit2
A419
Selector 1 Bit Mode
GE Multilin
RANGE
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
0 to 1
2 to 3
1 to 2
0 to 255
0 to 255
0 to 255
0 to 1
0 to 3
0 to 3
0 to 65535
0 to 65535
0 to 1
0 to 2
0 to 65535
0 to 2
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
1 to 7
1 to 7
0 to 1
1 to 7
3 to 60
0 to 65535
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
D60 Line Distance Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
---
F001
---
1
F086
---
1
F086
---
1
F300
---
1
F300
---
1
F126
---
1
F134
---
1
F001
---
1
F134
---
1
F001
---
1
F134
---
1
F500
---
1
F500
---
1
F108
---
1
F108
---
1
F102
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
0.1
F001
---
1
F300
---
1
F083
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F083
DEFAULT
0
0
0
0
B
0
0
0
0
0 (Disabled)
2
1
0
0
0
0
0 (Off)
0 (Off)
0
0
0 (No)
1 (OK)
0
1 (OK)
0
2 (n/a)
0
0
0 (Off)
0 (Off)
0 (Disabled)
0
1
0 (Disabled)
7
50
0
0 (Time-out)
0
0
0
0
0 (Time-out)
B-39