GE D60 Instruction Manual page 153

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
Table 5–6: D60 FLEXLOGIC™ OPERANDS (Sheet 4 of 8)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
NEUTRAL IOC1 PKP
Neutral
NEUTRAL IOC1 OP
Instantaneous
NEUTRAL IOC1 DPO
Overcurrent
NEUTRAL IOC2
ELEMENT:
NEUTRAL OV1 PKP
Neutral Overvoltage
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
ELEMENT:
NEUTRAL TOC1 PKP
Neutral Time
NEUTRAL TOC1 OP
Overcurrent
NEUTRAL TOC1 DPO
NEUTRAL TOC2
ELEMENT:
NTRL DIR OC1 FWD
Neutral Directional
NTRL DIR OC1 REV
Overcurrent
NTRL DIR OC2
OPEN POLE OP ΦA
ELEMENT:
OPEN POLE OP ΦB
Open Pole Detector
OPEN POLE OP ΦC
OPEN POLE BKR ΦA OP
OPEN POLE BKR ΦB OP
OPEN POLE BKR ΦC OP
OPEN POLE BLK N
OPEN POLE BLK AB
OPEN POLE BLK BC
OPEN POLE BLK CA
OPEN POLE REM OP ΦA
OPEN POLE REM OP ΦB
OPEN POLE REM OP ΦC
OPEN POLE OP
ELEMENT:
PH DIR1 BLK A
Phase Directional
PH DIR1 BLK B
Overcurrent
PH DIR1 BLK C
PH DIR1 BLK
PH DIR2
ELEMENT:
PH DIST Z1 PKP
Phase Distance
PH DIST Z1 OP
PH DIST Z1 OP AB
PH DIST Z1 OP BC
PH DIST Z1 OP CA
PH DIST Z1 PKP AB
PH DIST Z1 PKP BC
PH DIST Z1 PKP CA
PH DIST Z1 SUPN IAB
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
PH DIST Z1 DPO AB
PH DIST Z1 DPO BC
PH DIST Z1 DPO CA
PH DIST Z2 to Z5
ELEMENT:
PHASE IOC1 PKP
Phase
PHASE IOC1 OP
Instantaneous
PHASE IOC1 DPO
Overcurrent
PHASE IOC1 PKP A
PHASE IOC1 PKP B
PHASE IOC1 PKP C
PHASE IOC1 OP A
PHASE IOC1 OP B
PHASE IOC1 OP C
PHASE IOC1 DPO A
PHASE IOC1 DPO B
PHASE IOC1 DPO C
PHASE IOC2
GE Multilin
OPERAND DESCRIPTION
Neutral Instantaneous Overcurrent 1 has picked up
Neutral Instantaneous Overcurrent 1 has operated
Neutral Instantaneous Overcurrent 1 has dropped out
Same set of operands as shown for NEUTRAL IOC1
Neutral Overvoltage element has picked up
Neutral Overvoltage element has dropped out
Neutral Overvoltage element has operated
Neutral Time Overcurrent 1 has picked up
Neutral Time Overcurrent 1 has operated
Neutral Time Overcurrent 1 has dropped out
Same set of operands as shown for NEUTRAL TOC1
Neutral Directional OC1 Forward has operated
Neutral Directional OC1 Reverse has operated
Same set of operands as shown for NTRL DIR OC1
Open pole condition is detected in phase A
Open pole condition is detected in phase B
Open pole condition is detected in phase C
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase A
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase B
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase C
Blocking signal for neutral, ground, and negative-sequence overcurrent
element is established
Blocking signal for the AB phase distance elements is established
Blocking signal for the BC phase distance elements is established
Blocking signal for the CA phase distance elements is established
Remote open pole condition detected in phase A
Remote open pole condition detected in phase B
Remote open pole condition detected in phase C
Open pole detector is operated
Phase A Directional 1 Block
Phase B Directional 1 Block
Phase C Directional 1 Block
Phase Directional 1 Block
Same set of operands as shown for PH DIR1
Phase Distance Zone 1 has picked up
Phase Distance Zone 1 has operated
Phase Distance Zone 1 phase AB has operated
Phase Distance Zone 1 phase BC has operated
Phase Distance Zone 1 phase CA has operated
Phase Distance Zone 1 phase AB has picked up
Phase Distance Zone 1 phase BC has picked up
Phase Distance Zone 1 phase CA has picked up
Phase Distance Zone 1 phase AB IOC is supervising
Phase Distance Zone 1 phase BC IOC is supervising
Phase Distance Zone 1 phase CA IOC is supervising
Phase Distance Zone 1 phase AB has dropped out
Phase Distance Zone 1 phase BC has dropped out
Phase Distance Zone 1 phase CA has dropped out
Same set of operands as shown for PH DIST Z1
At least one phase of PHASE IOC1 has picked up
At least one phase of PHASE IOC1 has operated
At least one phase of PHASE IOC1 has dropped out
Phase A of PHASE IOC1 has picked up
Phase B of PHASE IOC1 has picked up
Phase C of PHASE IOC1 has picked up
Phase A of PHASE IOC1 has operated
Phase B of PHASE IOC1 has operated
Phase C of PHASE IOC1 has operated
Phase A of PHASE IOC1 has dropped out
Phase B of PHASE IOC1 has dropped out
Phase C of PHASE IOC1 has dropped out
Same set of operands as shown for PHASE IOC1
D60 Line Distance Relay
5.4 FLEXLOGIC™