Perform the following when using the FX5-4DA-ADP:
• Set the number of times of winding to "2 turns" within approximately 200 mm from the connectors of the power cable on the
FX5-4DA-ADP side, and attach a ferrite core. (Ferrite core used in our test: E04SR401938 manufactured by SEIWA
ELECTRIC MFG. CO., LTD.)
• The FX5-4DA-ADP requires that the cable used for power supply is 30 m or less.
Caution for when the built-in Ethernet port is used
• Use a shielded twisted pair cable for the 10BASE-T or 100BASE-TX cable. Strip a part of the jacket of the shielded twisted
pair cable as shown below and ground as much of the exposed shield as possible to both sides of the cable.
• Connect a ferrite core to both ends of the cable. (Ferrite core used in tests by Mitsubishi: ZCAT2035-0930A manufactured
by TDK Co.)
Shield
Clamp metal fitting
Ferrite core