Input Wiring Example - Mitsubishi Electric MELSEC iQ-F FX5U User Manual

Programmable controller
Hide thumbs Also See for MELSEC iQ-F FX5U:
Table of Contents

Advertisement

Input wiring example

Sink input [AC power supply type]
FX5U-32MT/ES
5V 0V 24V
FX5-16EX/ES
5V 0V 24V
FX5-16EX/ES
5V 0V 24V
*1 Handle the power supply circuit properly in accordance with "Power Supply Wiring."
*2 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
*3 In the case of sink input wiring, short-circuit the [S/S] and [24V] terminals of the CPU module.
The service power supply or external power supply can be used for all inputs (X) of the CPU module. However
you need to select either one for each CPU module or I/O module. Both power supplies cannot be used
together in the same module.
6 WIRING
108
6.5 Input Wiring
L
N
*3
S/S
0V
0V
24V
24V
X0
X1
Input
Input
terminal
impedance
S/S
X0
X1
Input
terminal
S/S
X0
X1
Input
terminal
Fuse
Class D grounding
Three-wire
sensor
Two-wire
proximity
*2
sensor
24 V DC
Three-wire
sensor
*1