Huawei NetCol5000-C User Manual page 117

Chilled water-cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-C:
Table of Contents

Advertisement

NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual
Alarm
Alarm Name
ID
a080
CW value
exceed
runtime
a083
SPD fault
a084
Power fault
a085
Route A fuse
disconnect
a086
Route B fuse
disconnect
Route C fuse
a087
disconnect
a088
Route D fuse
disconnect
a090
Cond pump
1/2 exceed
runtime
a091
Cold aisle LT
Issue 02 (2013-12-10)
System
Severity
Operation
Warning
The alarm is
generated.
The alarm is
Major
generated.
Critical
The alarm is
generated, and
the
NetCol5000-C
shuts down.
Critical
The alarm is
generated, and
the
NetCol5000-C
shuts down.
Critical
The alarm is
generated, and
the
NetCol5000-C
shuts down.
The alarm is
Critical
generated, and
the
NetCol5000-C
shuts down.
Critical
The alarm is
generated, and
the
NetCol5000-C
shuts down.
Warning
The alarm is
generated.
Warning
The alarm is
generated.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
5. The drainpipe of the
condensate pump is
blocked.
The accumulated runtime
of the CW value exceeds
the alarm set point.
1. The SPD is faulty.
2. Cables to the SPD are
loose or damaged.
A wrong power
distributor is used.
1. A device on loop A is
faulty.
2. The loop A fuse is
blown.
1. A device on loop B is
faulty.
2. The loop B fuse is
blown.
1. A device on loop C is
faulty.
2. The loop C fuse is
blown.
1. A device on loop D is
faulty.
2. The loop D fuse is
blown.
The accumulated runtime
of condensate pump
exceeds the alarm set
point.
1. The return-air low
temperature alarm set
point is inappropriate
for the working
conditions.
2. The temperature
displayed on the LCD
Recovery Measures
the drainpipe.
Maintain or replace the
CW value.
1. Maintain or replace
the SPD.
2. Check cables to the
SPD.
Maintain or replace the
power distributor.
1. Maintain or replace
the faulty device on
loop A.
2. Replace the loop A
fuse.
1. Maintain or replace
the faulty device on
loop B.
2. Replace the loop B
fuse.
1. Maintain or replace
the faulty device on
loop C.
2. Replace the loop C
fuse.
1. Maintain or replace
the faulty device on
loop D.
2. Replace the loop D
fuse.
Maintain or replace
condensate pump.
1. Adjust the return-air
low temperature
alarm set point.
2. Maintain or replace
the temperature and
humidity sensor.
3. Maintain or replace