[5-2 Outdoor Unit Control ]
5-2-13

Emergency Operation Mode

1. Problems with the outdoor unit
Systems with two outdoor units have a mode that allows one of the outdoor units to perform a backup operation when the
other outdoor unit in the system malfunctions.
This mode can be started by performing an error reset via the remote controller.
(1) Starting the emergency operation
1) When an error occurs, the error source and the error code will be displayed on the display on the remote controller.
2) The error is reset using the remote controller.
3) If an error code appears that permits an emergency operation in step 1) above, (See the table below.), the retry operation
starts.
4) If the same error is detected during the retry operation (step 3 above), an emergency operation can be started by resetting
the error via the remote controller.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Trouble source
Compressor
Fan motor
Inverter
Thermistor
TH2
TH3
TH4
TH5
TH6
TH7
TH9
TH11
TH12
Power
Emergency operation pattern (2 outdoor units)
1) If an attempt is made to put into operation a group of indoor units whose total capacity exceeds the maximum allowable ca-
pacity, some of the indoor units will go into the same condition as Thermo-OFF.
HWE1314A
Error codes that permit an
emergency operation
0403
4220,4225,4226
4230,4235
4240,4245
4250,4255,4256
5110
5301
5305,5306
5102
5103
5104
5105
5106
5107
5109
5111
5112
4102
4115
OC
OS
Emergency
operation
Maximum total capacity
of indoor units (Note 1)
Error code description
Serial communication error
Bus voltage drop
Heatsink overheat protection
Overload protection
Overcurrent relay trip
Heatsink temperature sensor failure (THHS)
Current sensor/circuit failure
Position error
Subcool heat exchanger bypass outlet temperature sensor failure
Pipe temperature sensor failure
Discharge temperature sensor failure
Accumulator inlet temperature sensor failure
Subcool heat exchanger liquid outlet sensor failure
Outside air temperature sensor failure
Continuous heating temperature sensor fault
Continuous heating temperature sensor fault
Continuous heating temperature sensor fault
Open phase
Power supply sync signal abnormality
OC failure
OS failure
pattern
pattern
Trouble
Normal
Normal
Trouble
Cooling
Permitted Permitted
Heating
Permitted Permitted
60%
- 146 -