Error Code [7113]
1. Error code definition
Function setting error (improper connection of CNTYP)
2. Error source, cause, check method and remedy
Error source
Outdoor unit
(1)
(2)
(3)
(4)
HWE1314A
Cause
Wiring fault
Loose connectors, short-cir-
cuit, contact failure
Incompatible control board
and INV board (replacement
with a wrong circuit board)
DIP SW setting error on the
control board
Check method and remedy
(Detail code 15)
1) Check the connector CNTYP5 on the control board for proper con-
nection.
(Detail code 14)
1) Check the connector CNTYP5 on the control board for proper con-
nection.
2) Check the settings of SW5-3 through SW5-6 on the control board.
(Detail code 12)
1) Check the connector CNTYP2 on the control board for proper con-
nection.
2) Check the connector CNTYP5 on the control board for proper con-
nection.
3) Check the settings of SW5-3 through SW5-6 on the control board.
(Detail code 16)
1) Check the connector CNTYP on the INV board for proper connec-
tion.
2) Check the connector CNTYP5 on the control board for proper con-
nection.
3) Check the settings of SW5-3 through SW5-6 on the control board.
4) Check the wiring between the control board and INV board.
Refer to the following page(s). [7-2-1 Error Code [0403]](page 226)
(Detail code 0, 1, 5, 6)
1) Check the wiring between the control board and INV board.
Refer to the following page(s). [7-2-1 Error Code [0403]](page 226)
2) Check the settings of SW5-3 through SW5-6 on the control board.
3) Check the connector CNTYP5 on the control board for proper con-
nection.
(Detail code Miscellaneous)
*If a set-model-name identification error occurs, check the detail
code on the unit on which the error occurred. The detail code that
appears on other units will be different from the ones shown
above.