Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook page 33

Table of Contents

Advertisement

[2-1 System Configurations ]
(2) High COP combinations
Outdoor units
EP200
YLM-A
EP250
YLM-A
EP300
YLM-A
EP350
YLM-A
EP400
YLM-A
EP450
YLM-A
EP500
YLM-A
EP500
YSLM-A
EP550
YSLM-A
EP600
YSLM-A
EP650
YSLM-A
EP700
YSLM-A
EP750
YSLM-A
EP800
YSLM-A
EP850
YSLM-A
EP900
YSLM-A
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE1314A
Composing units
-
-
-
-
-
-
-
-
-
-
-
-
-
-
EP250YLM-A
EP250YLM-A
EP300YLM-A
EP250YLM-A
EP300YLM-A
EP300YLM-A
EP350YLM-A
EP300YLM-A
EP350YLM-A
EP350YLM-A
EP400YLM-A
EP350YLM-A
EP400YLM-A
EP400YLM-A
EP450YLM-A
EP400YLM-A
EP450YLM-A
EP450YLM-A
Maximum total ca-
Maximum number
pacity of connect-
of connectable in-
able indoor units
100 - 300
125 - 375
150 - 450
175 - 525
200 - 600
225 - 675
250 - 750
250 - 750
275 - 825
300 - 900
325 - 975
350 - 1050
375 - 1125
400 - 1200
425 - 1275
450 - 1350
- 22 -
Types of connect-
able indoor units
door units
20
P15 - P250 models
R410A series in-
25
door units
30
35
40
45
50
GB