[2-10 Restrictions on Refrigerant Pipes ]
7) The maximum capacity of the indoor units that is connectable to the CMB-P-V-GB1 types of sub BC controllers is P350 or
below (when two GB1 type controllers are connected P350 or below for both combined) .
The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016V-HB1 is P350 or below.
If at least one CMB-P1016V-HB1 unit is connected, the maximum total capacity of connectable indoor units to a system with
two sub controllers is P450 or below.
Restrictions on pipe length
[PURY-(E)P200, 250YLM]
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
200
[656]
10
20
30
40
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m [ft])
[PURY-P400, 450YSLM, (E)P500, 550YSLM]
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
200
[656]
10
20
30
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m [ft])
[PURY-(E)P700, 750, 800, 850, 900YSLM]
1000
900
800
700
600
500
400
300
200
10
20
30
40
Distance between outdoor unit and BC controller(m)
HWE1314A
50
60
70
80
90
40
50
60
70
80
90
50
60
70
80
90 100 110
[PURY-(E)P300, 350, 400, 450, 500YLM]
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
200
[656]
100 110
10
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m [ft])
[PURY-(E)P600, 650YSLM]
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
200
[656]
10
100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m [ft])
The height difference and the pipe length between BC controller and indoor units
70
[229]
60
[196]
50
[164]
40
[131]
30
[98]
20
[64]
10
[32]
0
0
Vertical separation between the main BC controller and indoor units (m[ft])
- 58 -
20
30
40
50
60
70
20
30
40
50
60
70
5
10
[16]
[32]
80
90
100 110
80
90
100 110
15
[49]
GB