Power Up And Bind A Mixing Valve Controller (Hm80) - Honeywell evohome Installation Manual

Hide thumbs Also See for evohome:
Table of Contents

Advertisement

Mixing Valve Controller (HM80)
evohome
Controller
If you are NOT
following GUIDED
CONFIGURATION
follow these steps
on your evohome
Controller display
once the Mixing Valve
Controller and sensor
have been installed:
1. On the evohome
Controller press and
hold "Settings"
for
3 seconds
2. Press the green tick
3. Select ADD A ZONE
4. Select the zone you're
adding the controller
to then select MIXING
VALVE
5. If you want to control
the zone temperature
with your evohome
Controller (the
evohome Controller
needs to be located
in that zone) YES,
otherwise press NO
and bind the sensor.
evohome Installation Guide
Power up and bind a Mixing Valve
Controller (HM80)
A Mixing Valve Controller should only be fitted by a qualified
fitter. Unless you're using the evohome Controller as a sensor,
you need to install a sensor (HCW82, HCF82 or DTS92)
before binding the controller to the evohome Controller.
To bind the Digital Room
Temperature Sensor (DTS92)
Press and hold the power button for 2
1
seconds to put the unit into standby
Press the up and down arrows together for
2
three seconds – it should say INst
Press the down arrow – it should say COnt
3
Press the up arrow three times – it should say CLr
4
Press the power button once to clear
5
any previous binding data
Press the up arrow – it should say COnt
6
Press the power button once to send the
7
binding signal to the evohome Controller
You should receive a SUCCESS message on the
8
evohome Controller (if not go back and re-bind)
2
HOLD
3 SEC
CONTINUED ON NEXT PAGE
27