Honeywell Evohome Installation Manual page 22

Controller
Hide thumbs Also See for Evohome:

Advertisement

20
Wireless Relay Box (BDR91) continued
evohome
Controller
If you are NOT following
GUIDED CONFIGURATION
follow these steps on your
evohome Controller display
first:
1. Press and hold "Settings"
for 3 seconds
2. Press the green tick
3. Press ADD ZONE
4. Press the zone you want
to add the controller to
5. Rename the zone if
required and/or press the
green tick
6. Press ZONE VALVES
Step 3: Power up and bind devices
Power up and bind a Wireless Relay Box
(BDR91) to control a Zone Valve
Make sure the Wireless Relay Box (BDR91) is
wired to the Zone Valve and powered up.
If you want to control the zone temperature with the
evohome Controller (the evohome Controller needs
to be located in that zone) press YES, otherwise press
NO and bind a sensor – either Digital Room Thermostat
(DTS92) or Room Temperature Sensor (HCW82/HCF82).
To bind the Digital Room
Temperature Sensor (DTS92)
Press and hold the power button for 2
1
seconds to put the unit into standby
Press the up and down arrows together for
2
three seconds – it should say INst
Press the down arrow – it should say COnt
3
Press the up arrow three times – it should say CLr
4
Press the power button once to clear
5
any previous binding data
Press the up arrow – it should say COnt
6
Press the power button once to send the
7
binding signal to the evohome Controller
You should receive a SUCCESS message on the
8
evohome Controller (if not go back and re-bind)
2
HOlD
3 SEC