Honeywell 7000 Product Data page 6

Solid state alarm system
Table of Contents

Advertisement

HONEYWELL 7000 SOLID STATE ALARM SYSTEM
SYSTEM 7000
HOME CONTROL SYSTEM
HOME AND BUILDING CONTROL
MINNEAPOLIS, MINNESOTA
HOUSEHOLD FIRE AND BURGLARY WARNING SYSTEM.
U.L. HOME HEALTHCARE SIGNALING SYSTEM.
HOUSEHOLD BURGLARY U.L. GRADE A WHEN USED
WITH EXTERNAL AUDIBLE.
BEFORE INSTALLING, READ HONEYWELL SYSTEM 7000
INSTALLATION MANUAL, 69-1192 REV. 9/98.
BEFORE OPERATING, READ HONEYWELL SYSTEM 7000
OWNERS MANUAL.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH CHAPTER 2 OF NFPA STANDARD 72.
NATIONAL FIRE PROTECTION ASSOCIATION,
BATTERYMARCH PARK, QUINCY, MA 02269
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING, MAINTENANCE,
EVACUATION, PLANNING, AND REPAIR IS TO BE
PROVIDED WITH THIS EQUIPMENT.
THE SYSTEM IS U.L. LISTED FOR LIMITED ENERGY
INSTALLATIONS PER NEC ARTICLE 760.
USE ONLY U.L. RECOGNIZED LIMITED ENERGY CABLE.
TEST SYSTEM AT LEAST ONCE A WEEK WITH AC OFF.
SYSTEM SHOULD BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST EVERY THREE YEARS.
STANDBY BATTERY/BATTERIES SHOULD BE REPLACED
EVERY FIVE YEARS.
DISCONNECT AC LINES AND TELEPHONE WIRES
BEFORE SERVICING.
WARNING:
OWNERS INSTRUCTION NOTICE NOT TO BE
REMOVED BY ANYONE EXCEPT OCCUPANT.
TB 1
END OF LINE RESISTOR
CONNECTED ACROSS THE
HBUS+ AND HBUS–
CONTACTS OF LAST (END)
DEVICE CONNECTED TO
THE HBUS CIRCUIT
Fig. 4. Control panel wiring, showing TB1 and general physical layout.
69-1192—1
+
+
+
+
+
+
+
1
2
3
4
5
6
7
NC
NO
HSP
EOLR
PEM
3.3K 5% 1/4W
RFEM
TYPICAL FOR
POINTS P1 TO P7
EOLR
END-OF-LINE
RESISTOR MUST BE
AT END OF CONTACT.
120Ω 5% 1/4W
WARNING: LEAVING THE POWER SWITCH
IN THE OFF POSITION RENDERS THE SYSTEM
7000 CONTROL PANEL INOPERABLE.
WARNING: FOR CONTINUED PROTECTION
AGAINST FIRE, REPLACE FUSE WITH SAME
TYPE AND RATING (AGA 2)
TELCO LINE COUPLER CORD TO RJ31X.
CONNECT PC PROGRAMMER HERE FOR LOCAL
PROGRAMMING.
J1
CONNECT TO EARTH GROUND
+
+
+
+
+
+
+
+
8
9
10
11
12
13
14
15
1
AUXILIARY OUTPUT,
SMOKE DETECTOR
PROGRAMMABLE
VOFF = 25V MAX (FLOAT)
VON = 1.1V MAX
ISINK = 100 mA
SMOKE DETECTOR
5.1K 5% 1/4W
MAXIMUM OF 10 2-WIRE
SMOKE DETECTORS. REFER TO
INSTALLATION INSTRUCTIONS
69-1192 FOR A LIST OF
APPROVED DETECTORS.
SMOKE DETECTOR COMPATIBILITY
IDENTIFIER IS 7K8.
P8 MAY BE WIRED FOR 2-WIRE FIRE
OR 4-WIRE FIRE OR BURGLARY.
2-WIRE FIRE IS SHOWN. FOR
4-WIRE FIRE AND BURGLARY
WIRING, SEE INSTALLATION
INSTRUCTIONS.
6
S 1
AC
STANDBY BATTERY
MINIMUM REQUIREMENTS: 12 VDC, 7 AH
REFERENCE PART NUMBER 32002215-001
REPLACE BATTERY EVERY 5 YEARS.
SYSTEM SUPPLIES 4 TO 24 HR. EMERGENCY
STANDBY CAPACITY. 24 HOURS REQUIRED
FOR FIRE PROTECTION. SEE INSTALLATION
MANUAL 69-1192 REV 9/98 FOR EQUIPMENT
AND BATTERY CONFIGURATIONS.
1
+
+
+
+
+
+
+
16
17
18
19
20
21
22
+
+
+
BELL / HORN
12 VDC,
1 AMP MAX.
+
EOLR
PLUG-IN TRANSFORMER
PART NO.: 32002143-001
INPUT 120 VAC, 60HZ
OUTPUT: 24 VAC, 50 VA
CLASS 2
DO NOT CONNECT AC
TRANSFORMER TO A
SWITCH CONTROLLED
OUTLET.
97-5790 REV.
M10910

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents