Honeywell 7000 Product Data page 27

Solid state alarm system
Table of Contents

Advertisement

California State Fire Marshal (CSFM)
Requirements
24 hour battery back-up:
1. Per NFPA72, Battery backup capabilities must be
provided for 24 hours of normal service followed by at
least 4 minutes of File Alarm signaling
2. The maximum Ampere Hour Battery load for System
7000 is 28 AH without a Listed Auxiliary Power Supply.
3. The minimum Ampere Hour Battery is 7 AH and current
load is restricted to 210 milliamps normal standby and
1.185 amperes of alarm for 4 minutes for 24 hours of
battery backup.
4. Use ALARM-SAF AP/PS5BF12-UL when auxiliary
power is required on CSFM installations.
5. Use ADEMCO 747UL Sirens for audible
requirements.
Federal Communications Commission (FCC)
Statement
This equipment has been tested to FCC requirements and
has been found acceptable for use. The FCC requires the
following statement for your information:
This equipment generates and uses radio frequency energy
and if not installed and used properly, that is, in strict
accordance with the manufacturer's instructions, may cause
interference to radio and television reception. It has been type
tested and found to comply with the limits for Class B
computing device in accordance with the specifications in
Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference in a
residential installation. However, there is no guarantee that
interference will not occur in a particular installation. If this
equipment does cause interference to radio or television
reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
1. If using an indoor antenna, have a quality outdoor
antenna installed.
2. Reorient the receiving antenna until interference is
reduced or eliminated.
3. Move the receiver away from the control/communicator.
4. Move the antenna leads away from ant wire runs to the
control/communicator.
5. Plug the control/communicator into a different power
outlet so that it and the receiver are on different branch
circuits.
6. If necessary, the user should consult the dealer or an
experienced radio/television technician for additional
suggestions.
7. If necessary, consult the booklet entitled "Interference
Handbook", prepared by the FCC. It is available from
the U.S. Government Printing Office, Washington, DC
20402.
The user shall not make any changes or modifications to the
equipment unless authorized by the Installation Instructions
or User's Manual. Unauthorized changes or modifications
could void the user's authority to operate the equipment.
HONEYWELL 7000 SOLID STATE ALARM SYSTEM
This equipment complies with Part 68 of the FCC rules. On
the front cover of this equipment is a label that contains,
among other information, the FCC registration number and
ringer equivalence number (REN) for this equipment. If
requested, this information must be provided to the telephone
company.
The REN is needed to determine the quantity of devices that
may be connected to the telephone line. Excessive REN on
the telephone line may result in the devices not ringing in
response to an incoming call. In most, but not all areas, the
sum of the REN should not exceed five (5). To be certain of
the number of REN that may be connected to your telephone
line, add up the REN on your line and call the local telephone
company and verify that you are below the maximum limit for
your area.
If this equipment causes harm to the telephone network, the
telephone company will notify you in advance that temporary
discontinuance of service may be required. If advance notice
is not practical, the telephone company will notify the
customer as soon as possible. Also, you will be advised of
your right to file a complaint with the FCC if you believe
necessary.
The telephone company may make changes in its facilities,
equipment, operations, or procedures that could affect the
operation of the equipment. If this happens, the telephone
company will provide advance notice in order for you to make
the necessary modifications in order to maintain uninterrupted
service.
If trouble is experienced with this equipment, please contact
the manufacturer for repair and warrantee information.
If the trouble is causing harm to the telephone network, the
telephone company may request you to remove the
equipment from the network until the problem is resolved.
This equipment uses a RJ31X to connect the System 7000 to
the telephone network.
There are no user serviceable components in this product,
and all necessary repairs must be made by the manufacturer.
Other repair methods may invalidate the FCC registration on
this product.
This equipment cannot be used on telephone company-
provided coin service. Connection to Party Line Service is
subject to state tariffs.
This equipment is hearing-aid compatible.
When programming or making test calls to an emergency
number, prior to initiating alarms, briefly explain to the
Monitoring dispatcher the reason for the call. Perform such
test activities in the off-peak hours; such as early morning or
late evening.
27