For device configuration, there is a 10-pin DIP switch behind the cover of
the master power unit. The DIP switch is only read in once by the control
device at switch-on or when the mains returns. Before commissioning, the
DIP switch must be set to suit the application.
• Switch off mains supply and secure against accidentally being switched
back on.
• Remove the cover of the master power unit.
• Set configuration on the DIP switch.
The settings that can be made with the individual switches are described in
the following chapters.

4.2.1 Operating mode and load types

Thyro-A 1A and Thyro-A 2A
S1.1
OFF
ON
OFF
ON
Thyro-A 3A
S1.1
OFF
ON
OFF*
ON
Can be set with
THYRO-TOOL FAMILY
* Default setting

4.2.2 Control mode / Analog output

The highest value of the load voltage or load current is always used
for control and display. The total power is used for power control. If a
bus module or PC is connected, control mode and analog output can
be set separately, e.g. U control with I display.
S1.2
OFF
OFF
TAKT - Full wave switch principle
ON
ON
QTM - Half wave switch principle (Quick takt mode)
S1.2
Load type and load connection
OFF
OFF
TAKT, with delta or star without neutral conductor
ON*
VAR, with delta or star without neutral conductor
ON
VAR, with star with neutral conductor
TAKT, with delta or star with neutral conductor
41
Operating mode
None
VAR - Phase-angle principle
VAR, with open delta
TAKT, with open delta