AEG Thyro-A Operating Instructions Manual page 54

Thyristor power controller
Hide thumbs Also See for Thyro-A:
Table of Contents

Advertisement

For Thyro-A 2A (wih load in delta connection) a setting for load mo-
nitoring can be made according to the table below:
Tab. 7c Load monitoring
e.g.
parallel
I
load nom
load
I
type controller
resistors
number
1
100%
1
80%
1
60%
1
40%
1
20%
2
100%
2
80%
2
60%
2
40%
2
20%
3
100%
3
80%
3
60%
-
-
-
-
-
-
-
-
-
-
Load in delta connection
Recommen-
Resistance
ded setting
/
increase in
for Poti R205
case of fault
73%
31%
20%
-
Thyro-A 2A
X2.9 [V]
[0-10V]
in %
79.0%
3.95
63.0%
3.15
48.0%
2.40
32.0%
1.60
16.0%
0.80
88.0%
4.40
66.0%
3.30
50.0%
2.50
33.0%
1.65
17.0%
0.85
90.0%
4.50
72.0%
3.60
(54%)
2.70
-
- -
-
- -
-
- -
-
- -
-
- -
54
X2.9
ca.
[0-20mA]
turns
7.90
12.0
6.30
10.0
4.80
8.0
3.20
5.5
1.60
3.5
8.80
13.5
6.60
10.5
5.00
8.5
3.30
6.0
1.70
4.0
9.00
14.0
7.20
11.5
5.40
9.0
-
-
-
-
-