Technical Data - AEG Thyro-A Operating Instructions Manual

Thyristor power controller
Hide thumbs Also See for Thyro-A:
Table of Contents

Advertisement

9. Technical data

Type voltage ...H1
230V -57%* +10%
400V -57%* +10%
500V -57%* +10%
600V -57%* +10%
Type voltage ...H RL1 and ...H RLP1 without additional 24V
electronics supply
230V -15% +10%
400V -15% +10%
500V -15% +10%
600V -15% +10%
Type voltage ...H RL1 and ...H RLP1 with additional 24V
electronics supply
230V -57%
400V -57%
500V -57%
600V -57%
Additional electronics supply
The additional control voltage supply can be AC or DC (2 W per
device / 5VA / not grounded).
Normally the supply of the Master modules is sufficient.
24VAC +10% /-20%
24VDC +18V to +32V
Mains frequency
All types 47 Hz to 63 Hz;
Max. frequency change 5% per half wave
Load type
ohmic load
ohmic load with R
Î=3xI
(for ...H RLP1 + HRL 1 in VAR operation)
nom
Transformer load
Thyro-A 2A: symmetrical load
99V
172V
215V
258V
99V
172V
215V
258 V
/R
ratio up to 6, peak current limiting to
warm
cold
CAUTION
If grain oriented, cold rolled sheet metal is used, the
induction of the downstream transformer should not
exceed 1.45 T for mains overvoltage = 1.2 T nominal
induction.
* The 5 V voltage (for possible setpoint
potentiometer supply) on terminal X2.8
only works correctly in the -15% to + 10%
range of the type voltage.
82