3.10.2 Averaging for the analog output
In order to attain a finer line thickness for line recorders, for example,
the output signal can be smoothened if needed to suit the applica-
tion.
MEAN 100
3.10.3 Control limits
For operating modes TAKT and VAR, it is possible to set control limits
(end position limits).
For Takt
T
Maximum switch-on period
smax
T
Minimum switch-on period
smin
For VAR
V_IE
Front pulse end position
H_IE
Rear pulse end position
3.10.4 Controller parameters
The parameters of the controller can be adapted to the path if
needed.
Parameters
T
20
I
K
60
P
K
5
R
* Default setting
3.10.5 Mains load optimization
The time for software synchronization can be set (see page 68, Mains
load optimization).
(50Hz)
=>
(60Hz)
=>
Mains periods (default setting)
Controller I share
Controller P share
Controller amplification
Delay period after mains returns 10ms * 100 =
1000 ms
Delay period after mains returns 8.33ms * 100 =
833 ms
(Default setting: 100)
35