3. Operation
This chapter describes the operating elements of Thyro-A. For default settings see
chapter 8.2.

3.1 Configuration switch S1

A 10-pole DIP switch is situated at the front behind the hood. The individual switches
are marked from 1-10 starting from the bottom and must be set before operation
according to application. They are only read in by the Power Controller once when
switched on or with mains recovery. For safety reasons further operation is carried
out with the hood closed. (3.2).

3.1.1 Operating mode

S1-
1
2
0
0
1
0
0
1
1
1

3.1.2 Control types / analog output

S1-
3
4
5
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
With 2-phase devices the highest value of phase voltage or phase current is used for
control and display. All values are available through the bus module.
3.1.3 Live zero set point
S1-
6
0
1
Operating mode
none
TAKT - full wave switch operation
VAR - phase-angle operation
QTM - Quick takt operation
Control types
U
(UxU) Control
2
U
(U) Control
I
2
(IxI) Control
I
(I) Control
I
(I) Control
P
P Control
P
P Control
configurable
with Thyro-Tool
Signal level
0 - (20) mA
4 - (20) mA
Analog output
U - Display
U - Display
I - Display
I - Display
U - Display
P - Display
(H RLP)
I - Display
(H RLP)
configurable
with Thyro-Tool
75