Function Mode List When The Remote Operator Is Used - Hitachi J300 Series Instruction Manual

J300 series
Hide thumbs Also See for J300 Series:
Table of Contents

Advertisement

12.3
Function mode

Function mode list when the remote operator is used

• Function mode initial values and display contents
Initial display contents, initialization, and change ranges are displayed in the table
indicated below.
(Function mode 1)
Display
Function
sequence
No.
1
F-00
2
F-01
3
F-02
4
F-03
Input
voltage
5
F-04
6
F-05
constant
(NOTE 1)
NOTE 1: The motor constants R1, R2, L, M, J, Kp, Ti, and KPP vary with the capacity.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
(Function mode 2)
Function
Initialization display
name
contents
Base
F-BASE
frequency
setting
Maximum
F-MAX
frequency
setting
Start
Fmin
frequency
adjustment
Motor input AVR AC
voltage
setting
AVR
AVRDEC
function
for
decelera-
tion
Control
CONTROL
method
setting
Autotuning
AUX AUTO
Motor
setting
Motor data
AUX DATA
selection
Motor
AUX K
005.50 kW
capacity
setting
Motor pole
AUX P
count
setting
Motor
AUX R1
constant
R1 setting
Motor
AUX R2
constant
R2 setting
Motor
AUX L
13.16 mH
constant
L setting
Initialization
0060 Hz
60 Hz
0060 Hz
60 Hz
0.50 Hz
0.5 Hz
460 V
230/460
OFF
OFF
VC
VC
NOR
NOR
NOR
NOR
NOR: Old Hitachi
TMO: New
Rated capacity
of each inverter
4p
4p
1.004
Rated capacity
of each inverter
0.776
Rated capacity
of each inverter
Rated capacity
of each inverter
12-5
Setting, change
Setting contents
contents
30 to 120 (400)
• When 120 Hz is switched to
400 Hz by F-30, a frequency
more than 120 Hz can be set.
30 to 120 (400)
0.1 to 9.9
• The equipment starts running
at this set value.
200,215,220,230
• The motor input voltage is set.
/380,400,415
440,460,480
ON/OFF
• ON or OFF of the AVR
function for deceleration
is set. When dynamic
braking torque is necessary
for deceleration, OFF is set.
VC, VP1, VP2,
• VC, VP1, VP2, VP3:
VP3, SLV, V2
V/F characteristics
SLV:Sensorless vector control
V2:Sensor vector control
NOR/AUT/NRT
• At the first running after
autotuning measurement
operation is executed.
• The autotuning motor data
general purpose
before starting autotuning
measurement is data
Hitachi general
equivalent to NOR.
purpose
AUT: Auto-
tuning data
3.7 to 160
• Set a capacity smaller than the
rated capacity as capacity
2, 4, 6, 8
• The number of poles of the
motor to be used is set.
0 to 65.535
0 to 65.535
0 to 655.35
AUT/NRT is set, the
data.