The terminal board will be exposed when the front cover or terminal cover (450L/HF,
550L/HF) is removed. Wire the inverter in this state.
5.1

Wiring the Power Supply and Motor

G
(PE)
• The inverter will be damaged if the power supply is connected to the motor terminals
U(T1), V(T2) and W(T3), so be sure not to make any mistakes.
• If multiple motors are to be connected, be sure to attach a thermal relay to each motor.
NOTE 1: When changing the power supply of the motor between the inverter and commer-
Power
supply
NOTE 2: Install an earth leakage breaker at the input of the inverter. (Select an earth leak-
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
R
S
T
RB
(L1)
(L2)
(L3)
(RB)
Dynamic
braking
resistor
ELB
Power supply
cial power, be sure to install mechanically interlocked switches Mg1 and Mg2.
ELB
Mg0
age breaker whose sensitive current level is raised in high frequency range.)
When the cable length between the inverter and motor is long (more than 10 m),
the thermal relay may malfunction due to higher harmonics. Therefore, install an
AC reactor on the output side of the inverter or use a current sensor in place of the
thermal relay.
P
N
U
V
(+)
(-)
(T1)
(T2)
MOTOR
Braking Units
R (L1)
(T1) U
Inverter
S (L2)
(T2) V
T (L3)
(T3) W
5-3
W
G
(T3)
(PE)
Mg1
Motor
Mg2