Measurement method for output voltage

(L1)
(T1)
R
U
(L2)
(T2)
S
V
(L3)
(T3)
T
W
Fundamental wave effective value:
VAC=1.1×VDC
10-7
Motor
Diode 600 V 0.1 A min.
(200 V class)
1000 V 0.1 A min.
(400 V class)
220 kΩ
2W
VDC
300 V (200 V class)
600 V (400 V class)
moving-coil type