Figure 25 Graphic Representation Of Sample Low Flow Cutoff Action - Honeywell SMV 3000 User Manual

Smart multivariable transmitter
Hide thumbs Also See for SMV 3000:
Table of Contents

Advertisement

6.9
FlowConf Configuration - PV4,
Figure 25
Graphic Representation of Sample Low Flow Cutoff Action.
PV4 Range
GPM
%
1100
100
990
90
880
80
770
70
660
60
550
50
440
40
330
30
220
20
High Limit
165
15
110
10
Low Limit
55
5
0
0
ATTENTION
1/99
Flow Rate
Flow Rate
enters cutoff*
Time
The low flow cutoff action also applies for reverse flow in the negative
direction. For the sample shown in Figure 25, this would result in a low
limit of –55 GPM and a high limit of –165 GPM.
SMV 3000 Transmitter User's Manual
Continued
Output
During
%
mA
Cutoff
100
20.0
90
18.4
80
16.8
70
15.2
60
13.6
50
12.0
40
10.4
Flow rate
30
8.8
leaves
cutoff*
20
7.2
15
6.4
0/
10
5.6
4.0*
5
4.8
* During cutoff,
0
4.0
output equals 0%
Continued on next page
73

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents