A.5
Configuration,
DAMPING Parameter
Table A-8
ATTENTION
PIUOTDCF Parameter
CJTACT Parameter
After Point is Built
1/99
Continued
The damping value is a real number selection from the transmitter range
values shown in Table A-8 for a given SMV 3000 transmitter PV.
Damping Range Values for SMV 3000 Transmitter PVs
IF Process Variable Number is...
PV1 or PV2
PV3
PV4
The IOP may temporarily convert the entered damping value to a standard
damping enumeration until it accesses the transmitter's database.
This parameter represents the sensor fault detection ON/OFF selection for
PV3 only.
This parameter will apply for PV3 thermocouple input only. It defines
whether an internal cold-junction (ON) or an externally provided cold-
junction reference (OFF) is to be used.
Once you complete the point build for PV1, you can start building the
point for the next PV or go to the Detail display for the point you just built
and either upload the transmitter's database to the IOP or download the
IOP's transmitter database to the transmitter. See Section A-6 in this
Appendix and Section 7 in the PM/APM Smartline Transmitter
Integration Manual for operation data using the Universal Station.
SMV 3000 Transmitter User's Manual
THEN Damping Value can be ...
0.00, 0.16, 0.32, 0.48, 1.0, 2.0,
4.0, 8.0, 16.0, or 32.0 seconds
0.00, 0.3, 0.7, 1.5, 3.1, 6.3, 12.7, 25.5,
51.1, or 102.3 seconds
0.00, 0.5, 1.0, 2.0, 3.0, 4.0, 5.0, 10.0,
50.0, or 100.0 seconds
163