GE D20MX User Manual page 71

Version 1.20 revision 0
Hide thumbs Also See for D20MX:
Table of Contents

Advertisement

CHAPTER 5: CONFIGURING THE SOFTWARE
Procedure
D20MX HARDWARE USER'S MANUAL
To transfer a D20 or D200 device configuration to the D20MX:
In the event that you have selected dialog checkbox "Do not show this message again",
some of the following steps do not appear. Accordingly, ignore the affected steps.
1.
Start SGConfig.
Result: The Welcome to SGConfig screen appears.
2.
Choose the D20MX Factory Default Configuration file, SAG0001-02.7zip or SAG0002-
02.7zip. based on the following criteria:
If transferring a configuration containing B009 versions greater than 310 and
B021 versions greater than 912 use the file SAG0001-02.7zip
If transferring a configuration containing B009 versions less than or equal to 310
and B021 versions less than or equal to 912, use the file SAG0002-02.7zip.
3.
If the SAG0001 or SAG0002 default configuration has already been imported, go to
step 4 to open the default configuration. Otherwise perform these steps:
3.1.
Click GE button > Archive > Project > Restore.
Result: The Restore Project Details window appears.
3.2.
Click ... .
Result: The Choose a File window appears.
3.3.
Navigate to the DVD/CD drive > Configuration Files > SGConfig.
Result: The two files SAG0001-02.zip and SAG0002-02.zip appear in the dialog.
3.4.
Select the appropriate file based on your decision in step 2.
3.5.
Click OK.
Result: On completion a pop-up message appears (e.g. Project 'SAG0001' has
been restored).
3.6.
Click OK.
4.
Open the D20MX Factory Default Configuration SAG0001 or SAG0002: click GE >
Recent Projects > select SAG0001-02 or SAG0002-02.
5.
Copy the firmware definition from the factory default configuration to the project
containing the D20 configuration (if you had opted to upgrade the firmware in
ConfigPro, then this step is not necessary):
5.1.
Click anywhere on the main page of the project to deselect the device.
5.2.
Click the ribbon Configure group > Miscellaneous > Firmware Library.
Result: The Firmware Library window appears with the firmware definition
selected.
5.3.
Select SAN0001/002 or SAN0002/002 based on the decision taken in step 2.
5.4.
Click Copy.
Result: The Firmware Information window appears.
5.5.
Set the Project Name in the Copy To region to the project containing the D20
configuration.
5.6.
Click OK.
Result: The Firmware Information window closes.
5.7.
Click Close.
Result: The Firmware Library window closes.
6.
Export the RADIUS roles from the default configuration:
6.1.
Double-click the D20 device named FAC_DEF.
Result: The Application List popup appears.
6.2.
Double-click the WESMAINT II+ application.
Result: The WESMAINT II+ table icon set appears.
GE INFORMATION