120
Wesmaint cable [977-0300] could be used to connect the Wesmaint port at the
back of the D20MX chassis to the serial communication port of the PC.
2.
Set up the terminal emulator with the D20MX communications parameters.
2.1.
From ConfigPro, select Device > Communications > Communications
Options....
Result: The Communications Options window appears.
2.2.
Set the communication options:
– Baud Rate: 19200
– Parity: None
– Data Bits: 8
– Stop Bits; 1
2.3.
Connect to the D20MX device.
2.3.1. Right-click or click the device icon.
2.3.2. Select Device > Communications > Terminal Emulator.
2.3.3. Login to the D20MX terminal using the login and password. When logging
into the D20MX for the first time, use the default login and password
[Login: admin | Password: changeme].
Result: The D20M prompt appears.