APPENDIX D: USING CONFIGPRO WITH D20MX
D20MX HARDWARE USER'S MANUAL
2.3.4. Confirm that access is allowed by pressing the Enter key a couple of
times.
2.4.
Download [sync] the configuration from ConfigPro to the D20MX by pressing
the F7 key on the key board.
2.5.
Optionally you can set up the terminal emulator for faster download speed:
2.5.1. Login to the D20MX device through the ConfigPro Terminal Emulator.
Result: The D20M prompt appears.
2.5.2. Type baud 115200 and press Enter.
Result: The D20MX baud rate changes from 19200 to 115200.
2.5.3. Disconnect the D20MX from ConfigPro by selecting Communications >
Disconnect.
2.5.4. Open the communication properties by selecting Device >
Communications > Communications Options....
Result: The Communications Options window appears.
2.5.5. Change the baud rate to match 115200 by selecting the Software
Transmit and Software Receive options and then clicking OK.
2.5.6. Reconnect to and login to the D20MX. See step 2.3 [Connect to the
D20MX device].
2.5.7. Download [sync] the configuration from ConfigPro to the D20MX by
pressing the F7 key.
Result: The Download Configuration File progress bar appears.
2.6.
Restart the D20MX device when the download is complete by clicking Boot.
GE INFORMATION