Pump Configuration Parameters

Table 16 displays Pump configuration parameters. Use the left
and right arrows to switch between Central Heat, Boiler, DHW,
System, Auxiliary 1, and Auxiliary 2 pumps. The parameters
are the same for all pumps.
Pressing the Advanced Settings button brings up a number of
other advanced configuration options for each pump. Press
the Control Settings button to return to the screen shown in
Fig. 36.
Fig. 36. Pump configuration.
Table 16. Pump Configuration Parameters for
R7910 Hydronic System.
Parameter
Pump control
Auto
On
Pump output
Pump A
Pump B
Pump C
None
Pump start delay
___hour ___min ___sec
Overrun time
___hour ___min ___sec
*Table 60 on page 42 has more parameters listed.
Comment
19
NOTE: The R7911 Steam Control does not have pumps,
but the outputs are available to operate air damp-
ers or accessories. CH Pump, Boiler Pump and
System Pump are used for these output options.
Table 16a. Pump Configuration Parameters for R7911
Steam Modulation Configuration Parameters.
Parameter
Auxiliary pump control
Auxiliary pump is on when
Auxiliary pump output
Boiler pump control
Boiler pump output
Boiler pump overrun time
CH pump control
CH pump output
CH pump overrun time
System pump control
System pump output
System pump ourrun time
Pump exercise time
Comment
Auto
On
CH pump is ON
Slave command
Pump A
Pump B
Pump C
None
Auto
On
Pump A
Pump B
Pump C
None
0-600 seconds
0 = Not configured
Auto
On
Pump A
Pump B
Pump C
None
0-600 seconds
0 = Not configured
Auto
On
Pump A
Pump B
Pump C
None
0-600 seconds
0 = Not configured
0-600 seconds
0= Not configured