Operations
4.2 Functionality
The following are approved functions for the N16.
Drift Compensation
Connected Capabilities (CLSS gateway required for Connected Capabilities)
– CLSS gateway
– Remote access for diagnostics
– Remote communication session- requires FACP to be in service mode. Technician required on site
Service Mode
– Remote programming. Technician required on-site
Multiple Detector Operation
– Units employing multiple detector operation shall include a minimum of two detectors in each protected space and reduce the
detector installation spacing to 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA
Alarm Delay
Pre-signal
Alarm verification
Two-wire compatibility
– One alarm per initiating device circuit
Polling Style limitations
– Polling Style is FlashScan or CLIP (Classic Loop Protocol)
– All detectors and modules on an SLC may be programmed as FlashScan. All detectors and modules must be FlashScan type devices.
Maximum number of devices per SLC: 159 detectors, 159 modules.
– All detectors and modules on an SLC may be programmed as CLIP. Detectors and modules may be a mix of CLIP and FlashScan
type devices, but all must be programmed as CLIP. Maximum number of devices per SLC: 99 detectors, 99 modules.
– All detectors may be programmed as CLIP, all modules as FlashScan, on an SLC. Detectors may be a mix of CLIP and FlashScan
type devices, modules must all be FlashScan type devices. Maximum number of devices per SLC: 99 CLIP detectors, 159 FlashScan
modules.
NAC Resound
Primary power source failure indication
CGW-MB Communication Format
– TCP/IP
Interconnected control panels
– Alarm, supervisory, and trouble conditions, as well as reset, alarm silence, or trouble silence actuation originating at this panel are
annunciated at this panel.
Integrated/network local functionality
Circuit disables
Network Mapping
Detection/alarm algorithms
Day/night sensitivity
Detection sensitivity adjustment
Extent/limitations of combination system
– Priority of signals
58