Bluetooth Led Status; Bacnet™ Ms/Tp Led Status; Modbus Led Status - Honeywell Unitary Installation Instructions Manual

Controller-230 vac
Table of Contents

Advertisement

HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS

Bluetooth LED Status

LED Status
OFF
Green LED
permanent ON
Green LED, 2 blinks
in 1 sec followed by
2 sec pause and
repeat
Red LED
permanent ON
BACnet™ MS/TP LED Status
LED Status
Green LED
permanent ON
Yellow LED
permanent ON
Red LED
permanent ON

Modbus LED Status

LED Status
Green LED
permanent ON
Yellow LED
permanent ON
Red LED
permanent ON
LED OFF
31-00610-01
Table 23 Bluetooth LED Status
Visual
Table 24 BACnet™ MS/TP LED Status
Visual
Table 25 Modbus LED Status
Visual
36
Mode
BLE disabled
BLE normal operation and connected
BLE enabled but not connected
BLE failure
Mode
Controller MS/TP BACnet communication is
normal.
Controller is sending MS/TP BACnet packets but
not receiving any response.
No communication from MS/TP BACnet. The
controller is not in the MS/TP network.
Mode
Modbus Communication is healthy - Successful
to read/write all of Modbus registers configured
in the application.
Modbus Communication is not healthy - failure to
read/write some of Modbus registers configured
in the application.
Modbus Communication failure - failure to
read/write all of Modbus registers configured in
the application.
No Modbus Communication - Application does
not have any Modbus read/write registers.