BACNET™ MS/TP CONTROLLER
BACnet™ MS/TP Limitations
There are two limitations regarding the number of
controllers per BACnet™ MS/TP network:

Physical Limitation

One Honeywell Unitary controller represents 1/8 load
(32 loads per TIA/EIA-485 standard). The physical
limitation is important if third party devices
representing a full load are connected.

AutoMAC limitation

A maxMaster of 127 means we can support a maximum
of 125 BACnet™ MS/TP Unitary controllers, one
supervisor, and one BACnet™ client (tool) per BACnet™
MS/TP network.
Table 18 Default Values
Default
Default
Max Master
MinMAC
127
1
NOTE:
1 and 127 are special MAC address reserved for
auto MAC addressing.
Depending on the actual performance needs and
required communication rates, connecting a smaller
number of BACnet™ MS/TP devices per network is
recommended.
NOTE:
It is recommended not to have more than 62
controllers on single MS/TP channel.

Automatic MAC Addressing

In contrast to other controllers, the Honeywell Unitary
controller features automatic MAC addressing.
The MAC addresses which the individual controllers in
the BACnet™ MS/TP channel assign to themselves is
not assigned in sequential order. Rather, they assign the
MAC Addresses in the range of min MAC to max MAC
(these are exposed as the proprietary properties ID
1028 (min MAC) and 1029 (max MAC) under device
object) currently not in use by another device in the
BACnet™ MS/TP channel (the MAC Address of "0" is
reserved by default for the router/plant controller,
itself).
HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS
Default
Default
Baud
MaxMAC
Rate
127
38400
All Honeywell Unitary controllers are BACnet™ MS/TP
clients. Every client performs periodic polling for the
possible appearance of new clients. Each client "knows"
the identity of the "next" client (for example, that
Honeywell Unitary controller with the next-highest MAC
Address) on the BACnet™ MS/TP bus and to which it
must therefore pass the token. The polling processes
includes a search for new clients which might have MAC
addresses lying between its own MAC address and that
of the "next" controller.
The property maxMaster specifies the highest allowable
address for controllers. The maxMaster is set to 127 by
default, thus guaranteeing that, on a BACnet™ MS/TP
bus the following properties are writeable and can be
changed:
• maxMaster
• min MAC
• max MAC
• MAC address
NOTE:
Do not attempt to program a MAC address outside
the range of min MAC and max MAC.
ROOM
1
2
3
4
5
6
7
8
9
1
11 12 13 14 15
16
17 18 19
2
21 22 23
32 33 34 35 36 37 38
1
2
3
4
5
6
7
8
9
1
11 12 13 14 15
16
17 18 19
2
21 22 23
32 33 34 35 36 37 38
V
NC1 NO1 IN1 NC2 NO2 IN2 NC3 NO3 IN3 NC4 NO4 IN4
AUX
OUT
SRIN
SR1
C
SR2
SR3
C
SR4
IO13 C IO14 IO15 C IO16
POWER 24V
DO RELAY
DO SSR
UIO
1
RS485
RS485
RS485 1
SYLK
UIO
24VDC
PORT1
PORT2
+
COM
-
24V
C
WM1 / 2
IO1 C IO2 IO3 C IO4 IO5 C IO6 IO7 C IO8 C
OUT
IO9 C
IO1
IO11 C IO12
10/100 SWITCHED
45
46
47 48 49 50 51 52 53
54
55 56 57 58 59
6
61 62 63
64
65
66 67 68 69
7
71 72
45
46
47 48 49 50 51 52 53
54
55 56 57 58 59
6
61 62 63
64
65
66 67 68 69
7
71 72
Fig. 24 Automatic MAC Addressing

Setting the MS/TP MAC Address

The MS/TP MAC address for each device must be set to
a unique value in the range of 1-127 on an MS/TP
network segment (addresses 1, 2, & 3 should be avoided
as they are commonly used for the router, diagnostic
tools, and as spare addresses). A seven-position DIP
switch on the BACnet™ MS/TP controller sets the MAC
address.
NOTE:
DIP setting of all-ON (MAC address will be 127) or
all-OFF (MAC address will be 1) will enable the
Auto MAC mode in the controller. The dip switches
will not be used for MAC addressing.
27
1
2
3
4
5
6
7
8
9
1
11 12 13 14 15
16
17 18 19
2
21 22 23
32 33 34 35 36 37 38
1
2
3
4
5
6
7
8
9
1
11 12 13 14 15
16
17 18 19
2
21 22 23
32 33 34 35 36 37 38
AUX
V
NC1 NO1 IN1 NC2 NO2 IN2 NC3 NO3 IN3 NC4 NO4 IN4
OUT
SRIN
SR1
C
SR2
SR3
C
SR4
IO13 C IO14 IO15 C IO16
POWER 24V
DO RELAY
DO SSR
UIO
1
RS485
RS485
RS485 1
SYLK
UIO
24VDC
PORT1
PORT2
+
COM
-
24V
C
WM1 / 2
IO1 C IO2 IO3 C IO4 IO5 C IO6 IO7 C IO8 C
OUT
IO9 C
IO1
IO11 C IO12
10/100 SWITCHED
45
46
47 48 49 50 51 52 53
54
55 56 57 58 59
6
61 62 63
64
65
66 67 68 69
7
71 72
45
46
47 48 49 50 51 52 53
54
55 56 57 58 59
6
61 62 63
64
65
66 67 68 69
7
71 72
31-00610-01

Advertisement

Table of Contents
loading

Table of Contents