Switching Between Two Motors

 How to drive two different motors with different settings?
Q
 How to store separate setting configurations for two different motors?
 How to change between setting configurations for batch production?
 Turn the "2nd-motor control [SET]" for the input terminal function on to change target
A
parameters. This function makes it possible to switch between different parameter
configurations to control two different types of motors.
 The "2nd-motor control is selected [SETM] (60)" output terminal function turns on when the
[SET] function is turned on.
 Parameters in the 200s parameter number of function groups A, b, C, and H are the second
control parameters.
(Example) The second control parameter corresponding to the "Frequency input source selection,
1st-motor [A001]" is the "Frequency input source selection, 2nd-motor [A201]".
 These parameters do not change, even when changing [SET] during inverter operation. In this
!
case, parameters change after the output is cut off.
 Please allow at least one second for changes to occur if you want to switch the [SET] terminal
and immediately run operations.
Code
[C001]
Input terminal
to
function
[C007]
[C021]
Output terminal
[C022]
function
[C026]
List of parameters switched by turning [SET] on/off
1st/2nd code
F002
F202
Acceleration time 1 setting or monitor
F003
F203
Deceleration time 1 setting or monitor
A001
A201
Frequency input source selection
A002
A202
RUN command input source selection
A003
A203
Base frequency
A004
A204
Maximum frequency
A020
A220
Multi-speed 0
Torque boost mode selection
A041
A241
A042
A242
Manual torque boost value
Manual torque boost peak speed
A043
A243
A044
A244
Control mode selection
A045
A245
Output voltage gain
A046
A246
Automatic torque boost voltage compensation gain
A047
A247
Automatic torque boost slip compensation gain
A061
A261
Upper frequency limit
Lower frequency limit
A062
A262
A081
A281
AVR function selection
Motor rated voltage
A082
A282
A092
A292
Acceleration time 2
A093
A293
Deceleration time 2
A094
A294
Accel/Decel change trigger selection
A095
A295
Accel1 to Accel2 frequency transition point
A096
A296
Decel1 to Decel2 frequency transition point
Item
2nd-motor control [SET]:
Turn this function on to switch to the second control
parameter.
2nd-motor control is selected [SETM]:
After [SET] is turned on, switching to the second
control parameter turns this signal on.
Item
9-7-18
Inverter Functions
Description
1st/2nd code
b012
b212
Electronic thermal level
b013
b213
Electronic thermal characteristics selection
b021
b221
Overload restriction 1 mode selection
b022
b222
Overload restriction 1 active level
b023
b223
Overload restriction 1 action time
C041
C241
Overload warning level
H002
H202
Async. Motor constant selection
Async. Motor capacity
H003
H203
H004
H204
Async. Motor number of poles
Async. Motor speed response
H005
H205
H006
H206
Async. Motor stabilization constant
H020
H220
Async. Motor constant R1
H021
H221
Async. Motor constant R2
H022
H222
Async. Motor constant L
H023
H223
Async. Motor constant I0
Async. Motor constant J
H024
H224
H030
H230
Async. Motor constant R1 (auto-tuning data)
Async. Motor constant R2 (auto-tuning data)
H031
H231
H032
H232
Async. Motor constant L (auto-tuning data)
H033
H233
Async. Motor constant I0 (auto-tuning data)
H034
H234
Async. Motor constant J (auto-tuning data)
Data
08
60
Item