Managing Pipe Sensor Thresholds - Honeywell TC300 Configuration And User's Manual

Commercial thermostat
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Heating
type
Fan Delay

Managing Pipe sensor thresholds

This feature is suitable for heating when pipe temperature is above threshold, and
suitable for Cooling when pipe temperature is below threshold.
To configure Pipe sensor thresholds
1. Swipe left from the Home screen.
2. On the Quick access screen, tap
The Pipe Sensor Thresholds screen appears.
Operation Configuration
Heat/Cool
Thresholds
(Standard)
Managing Pipe sensor thresholds
Table 25: Heating options (Continued)
Configuration
Range
Type
Fan On Delay
0 to 30 Sec
Time
Default 30
Fan Off Delay
0 to 180 Sec
Time
Default 120
Sec
Figure 54 Pipe Sensor Thresholds
Table 26: Pipe sensor threshold
Range
Type
Pipe Sensor
70 to 90°F (Default
Threshold for
80°F)
Heating
Pipe Sensor
45 to 65°F (Default
Threshold for
60°F)
Cooling
MANAGING PIPE SENSOR THRESHOLDS
Description
Fan on delay time after heating outputs are turned
on. May be used to run fan after heating outputs
have turned on for some times so that heating coil
can warm up.
Fan run on time after all heating outputs are turned
off. May be used to run fan after all heating outputs
have turned off so that the heat coil can cool down
before the fan turns off.
> Advanced > Pipe Sensor Thresholds.
Description
When the pipe temperature is above the
threshold, it is suitable for heating.
When the pipe temperature is below the
threshold, it is suitable for cooling.
75