Honeywell TC300 Configuration And User's Manual page 82

Commercial thermostat
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

4 - CONFIGURATION
3. Tap the BACnet MS/TP.
The BACnet MS/TP screen appears.
4. Tap BACnet MS/TP and enable it.
The BACnet MS/TP range screen appears.
5. The device automatically adapts to the baud rate of the MS/TP network. You can also
manually select the Baudrate
6. Enter a unique Device ID for the thermostat. It should be different from other TC300
thermostats.
7. Auto-MAC addressing is enabled by default, Installer can also manually set a unique
MAC address for the TC300.
Note:
The baud rate can be manually configured only after initial 5 minute delay.
8. To do manual configuration, tap Manual.
A text box appears below to enter the manual MAC address.
9. Tap Baud Rate, to select a desired baud rate from the list.
82
Figure 65 BACnet MS/TP
Figure 66 BACnet MS/TP
Managing connection