Honeywell TC300 Configuration And User's Manual page 53

Commercial thermostat
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

4-Pipe Single Coil
2. Tap 4-Pipe Single Coil.
The 4-Pipe Single Coil screen appears.
Regulating and changeover On/Off
Changeover
6-Way Valve
Note:
If Output is set to 0-10 Vdc
- Heating Rage: 0.0-4.7 Vdc
- Cooling Range: 5.3-10.0 Vdc
- Off voltage is 4.7-5.3Vdc
Equipment configuration
Valve
Valve type
operation/
Output
Floating
Modulating
Energize on
heat
Energize on
cool
2-10V
0-10V
Table 20: 4-Pipe single coil
Options
Normally open
Set Valve output type as N.C
Normally close
Set Valve output type as N.O
-
Modulating
control
Modulating
setting
-
Set Changeover relay type
-
Set Changeover relay type
Cooling Range
Heating Range
Reverse
Exchange the heating range and
cooling range
Cooling Range
Heating Range
Reverse
Exchange the heating range and
cooling range
EQUIPMENT CONFIGURATION
Description
Set output type Direct or Reverse
Set output type Direct or Reverse
Set Min position when enabled
Enable sync at mid night
Min output when enabled
Use Stage 1 cool as enabled
Set output type Direct or Reverse
Set Min output of Modulating
valve
Set Max output of Modulating
valve
Configure Min Output for Cooling
Configure Max Output for Cooling
Tap the Info icon to view the
minimum allowed deadband
range
Configure Min Output for Heating
Configure Max Output for Heating
Configure Min Output for Cooling
Configure Max Output for Cooling
Tap the Info icon to view the
minimum allowed deadband
range
Configure Min Output for Heating
Configure Max Output for Heating
53