Honeywell UDC2800 Product Manual page 401

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Chapter 12 - Standard Modbus Read, Write and Override Parameters
Parameter Description
Current Segment Number
Segment Time Remaining
Status
401
Register Address
Hex
Decimal
1E42
47747
1E48
47753
1E4B
47756
Access
Description
value
(engineering
unit)
R
Floating Point;
1...Max
Segment #
A write changes
the segment
number
R
Floating Point
in Seconds or
Time Units
R
Bit 0: 1=Ready
1: 1=Run
2: 1=Hold
3: 1=End
4: 1=Time Units
in Seconds
5: 1=Time Units
in Minutes
6: 1=Time Units
in Hours
7: Ramp Units
0: Time
l
1: Rate
l
8: If bit 7 Set
0: EU/Hour
l
1:
l
EU/Minute

Advertisement

Table of Contents
loading