PROGRAMMING AND SOFTWARE
Whitney Even on 06/22/2022
• Autoprogramming (learn mode) reduces installation time
• Custom English labels (per point) may be manually entered or
selected from an internal library file
• Two programmable Form-C relay outputs
• 99 software zones
• Continuous fire protection during online programming
• Program Check automatically catches common errors not linked
to any zone or input point
• OFFLINE PROGRAMMING: Create the entire program in your
office using FS-Tools, a Windows®-based software package, and
upload/download system programming locally. Offline program-
ming requires an ethernet connection. FS-Tools is available on
www.firelite.com.
User interface
LED INDICATORS
• Fire Alarm (red)
• CO Alarm (red)
• AC Power (green)
• Supervisory (yellow)
• Trouble (yellow)
• Ground fault (yellow)
• Battery fault (yellow)
• Disabled (yellow)
• Maintenance (yellow)
• Communication (yellow)
• Alarm Silenced (yellow)
• F1-F4 Programmable Function Keys (yellow)
KEYPAD
• 16 key alpha-numeric pad
• Acknowledge
• Alarm Silence
• Drill (Manual Evacuate)
• Four (4) programmable function keys
• Reset (lamp test)
PRODUCT LINE INFORMATION
ES-200X: Addressable Fire Alarm Control Panel with one SLC loop.
Includes main circuit board with display, pre-installed communicator,
chassis with transformer, backbox with door, plastic bag containing
screws, cables, key, etc. (For ES-200XC, refer to DF-60958.)
FS-Tools: Programming software for Windows®-based PC com-
puter. Available for download at www.firelite.com.
CELL-CAB-FL/CELL-MOD: Optional GSM communicators.
IPOTS-COM: Dual technology (POTS and IP) communicator.
(replacement board)
DP-ES-R: Optional dress panel for the ES-200X.
TR-CE: Optional trim ring for semi-flush mounting.
BB-2F: Optional cabinet for one or two modules.
BB-6F: Optional cabinet for up to six modules mounted on CHS-6
chassis.
BB-26: Battery backbox, holds up to two 25 AH batteries and CHG-
75.
BB-55F: Battery box, houses two 55 AH batteries
CHS-6: Chassis, mounts up to six multi-modules in a BB-6F cabinet.
CHG-75: Battery charger for lead-acid batteries with a rating of 25 to
75 AH.
CHG-120F: Remote battery charging system for lead-acid batteries
with a rating of 55 to 120 AH. Requires additional BB-55F for mount-
ing.
BAT Series: Batteries, see data sheet DF-52397.
Page 2 of 4 — DF-60957:A • 1/8/2018
PRN Series: UL listed compatible event printer. Uses tractor-fed
paper.
OPTIONAL MODULES
4XTMF Reverse Polarity Transmitter Module: Provides a super-
vised output for local energy municipal box transmitter, alarm and
trouble. Includes a disable switch and disable trouble LED.
PWRMOD24 Power Expander Module: Optional power module.
Increases alarm power output to 6 amps.
COMPATIBLE ANNUNCIATORS
ANN-80: Remote LCD annunciator mimics the information dis-
played on the FACP LCD display. Recommended wire type is un-
shielded.
ANN-100: Remote LCD annunciator mimics the information dis-
played on the FACP LCD display. Recommended wire type is un-
shielded. For use in FM applications only.
ANN-I/O: LED Driver Module provides connections to a user sup-
plied graphic annunciator. (See DF-52430.)
ANN-LED: Annunciator Module provides three LEDs for each zone:
Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF-
60241.)
ANN-RLED: Provides alarm (red) indicators for up to 30 input zones
or addressable points. (See DF-60241.)
ANN-RLY: Relay Module provides 10 programmable Form-C relays.
Can be mounted inside the cabinet. (See DF-52431.)
ANN-S/PG: Serial/Parallel Printer Gateway module provides a con-
nection for a serial or parallel printer. (See DF-52429.)
ADDRESSABLE DEVICES
All feature a polling LED and rotary switches for addressing.
SD365: Addressable low-profile photoelectric smoke detector. Lite-
Speed only.
SD365-IV: Addressable low-profile photoelectric smoke detector.
Ivory. LiteSpeed and CLIP mode.
SD365T: Addressable low-profile photoelectric smoke detector with
thermal sensor. LiteSpeed only.
SD365T-IV: Addressable low-profile photoelectric smoke detector
with thermal sensor. Ivory. LiteSpeed and CLIP mode.
SD365R: Remote test capable addressable photoelectric smoke
detector for use with DNR(W) duct detector housing. LiteSpeed only.
SD365R-IV: Remote test capable addressable photoelectric smoke
detector for use with DNR(W) duct detector housing. Ivory. Lite-
Speed and CLIP mode.
H365: Low-profile 135°F fixed thermal sensor. LiteSpeed only.
H365-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed
and CLIP mode.
H365R: Low-profile, intelligent, rate-of-rise thermal sensor. Lite-
Speed only.
H365R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. Ivory.
LiteSpeed and CLIP mode.
H365HT: Low-profile intelligent 190°F/88°C fixed thermal sensor.
LiteSpeed only.
H365HT-IV: Low-profile intelligent 190°F/88°C fixed thermal sensor.
Ivory. LiteSpeed and CLIP mode.
Legacy Devices
CP355: Addressable low-profile ionization smoke detector.
SD355: Addressable low-profile photoelectric smoke detector.
SD355T: Addressable low-profile photoelectric smoke detector with
thermal sensor.
SD355R: Remote test capable addressable photoelectric smoke
detector for use with DNR(W) duct detector housing.
SD355CO: Addressable, low-profile device that provides fire, heat,
and carbon monoxide (CO) detection.
H355: Fast-response, low-profile heat detector.

Hide quick links: