MDF-300(A) Dual Monitor Module
Whitney Even on 06/22/2022
The MDF-300(A) Dual Monitor Module is intended for use in
intelligent, two-wire systems. It provides two independent two-
wire initiating device circuits (IDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices. The module has a single panel-
controlled LED.
NOTE: The MDF-300(A) provides two Style B (Class B) IDC cir-
cuits ONLY. Style D (Class A) IDC circuits are NOT supported in
any application.
MDF-300(A) SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 μA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 μA
EOL resistance: 47K ohms.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
MDF-300(A) AUTOMATIC ADDRESSING
The MDF-300(A) automatically assigns itself to two address-
able points, starting with the original address. For example, if
the MDF-300(A) is set to address "26", then it will automati-
cally assign itself to addresses "26" and "27".
NOTE: "Ones" addresses on the MDF-300(A) are 0, 2, 4, 6, or 8
only. Terminals 6 and 7 use the first address, and terminals 8 and
9 use the second address.
CAUTION:
!
Avoid duplicating addresses on the system.
Installation
MMF-300(A), MMF-302(A), and MDF-300(A) modules mount
directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm)
deep, electrical box. They may also be mounted to the
SMB500 surface-mount box. Mounting hardware and installa-
tion instructions are provided with each module. All wiring
must conform to applicable local codes, ordinances, and regu-
lations. These modules are intended for power-limited wiring
only.
The MMF-301(A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
• UL: S2424
• ULC: S2424
• FM Approved
• CSFM: 7300-0075:0185
• MEA: 72-01-E
Product Line Information
NOTE: "A" suffix indicates ULC-listed model.
MMF-300(A): Monitor module.
MMF-301(A): Monitor module, miniature.
MMF-302(A): Monitor module, two-wire detectors.
MDF-300(A): Monitor module, dual, two independent Class B
circuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51309.
Architects'/Engineers' Specifications
Specifications of these devices and all FireLite products are
available from FireLite.