Architect/Engineer Specifications
General
L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1
octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 1
mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be
used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series
products, when used with the Sync•Circuit
and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185.
Strobe
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature
Humidity Range
Strobe Flash Rate
Nominal Voltage
Operating Voltage Range
Operating Voltage Range MDL3 Sync Module
Input Terminal Wire Gauge
Wall-Mount Dimensions (including lens)
Compact Wall-Mount Dimensions (including lens)
Horn Dimensions
Compact Horn Dimensions
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd.
Module accessory, shall be powered from a non-coded notification appliance circuit output
32°F to 120°F (0°C to 49°C)
10 to 93% non-condensing
1 flash per second
Regulated 12 DC or regulated 24 DC/FWR
8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
12 to 18 AWG
5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D)
5.26" L x 3.46" W x 1.91" D (133 mm L x 88 mm W x 49 mm D)
5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D)
5.25" L x 3.45" W x 1.25" D (133mm L x 88mm W x 32mm D)
/
-inch back box, 4 × 4 × 1½-inch back box, 4-inch
7
8
-inch back box. A universal
7
8
1,2