Implementing Thermal Overload And Short-Circuit Protection; Protecting The Drive And Input Power Cable In Short-Circuits; Protecting The Motor And Motor Cable In Short-Circuits - ABB ACS880-07C Hardware Manual

Table of Contents

Advertisement

Implementing thermal overload and short-circuit
protection

Protecting the drive and input power cable in short-circuits

The drive is equipped with internal AC fuses (1) as standard. The fuses restrict drive
damage and prevent damage to adjoining equipment in case of a short-circuit inside the
drive.
Protect the input cable with fuses or circuit breaker (2) according to local safety
regulations, appropriate input voltage and the rated current of the drive (see chapter
Technical
data).
2

Protecting the motor and motor cable in short-circuits

The drive protects the motor cable and motor in a short-circuit situation when the motor
cable is sized according to the nominal current of the drive. No additional protection
devices are needed.
Guidelines for planning the electrical installation 61