Appendix A: Ademco Contact Id Format Event Code Descriptions; A.1: Transmission Format Between Dact And Receiver; A.2: Ademco Contact Id Typical Printout - Honeywell GF505 Manual

Fire alarm control panels
Table of Contents

Advertisement

Appendix A: Ademco Contact ID Format Event Code Descriptions

This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format.
A.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC
SSSS= Four digit Subscriber ID Account Code
18= Identifies transmission as Contact ID to the receiver at the Central Station
Q= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ= Event code
GG= Group number
CCC= Zone number
Notes:
1.
18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the alarm and trouble
report.
2.
GG Group Number is fixed at '00' and cannot be changed.
3.
CCC for Zone Number is transmitted as '001' for zone 1 up to '010' for zone 10
A.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the Ademco Contact ID
Reporting Structure follows:
Time
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
Notes:
1.
11 is an example of a Receiver/Line Card, showing which receiver and line card the message was transmitted to.
2.
Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or R for New Restore.
100
ALARMS
Medical
Fire
Panic
Burglary
General
24 Hour
EVENT
Medical Alarms - 100
100 Medical
101 Pendant Transmitter
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
where
Date
Rcvr/Line ID
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
03/25
11
EVENT CODE CLASSIFICATIONS
200
300
SUPERVISORY
TROUBLES
Fire
System
Sounder/Relay
System Peripheral
Communication
Protective Loop
Sensor
SSSS
QXYZ
GG
7777
E110
00
7777
E111
00
7777
E380
00
7777
E570
00
7777
R110
00
7777
R111
00
7777
R380
00
7777
R570
00
7777
E158
00
7777
E151
00
400
OPEN/CLOSE
REMOTE ACCESS
Open/Close
Remote Access
Access Control
MESSAGE
EMERG - Personal Emergency - #
EMERG - Personal Embergency - #
CCCC
C001 - general fire alarm on zone one
C002 - smoke detector alarm on zone two
C003 - fault on zone three
C009 - Zone nine disabled
C001 - Zone one alarm restored
C002 - smoke detector zone two restored
C003 - zone three fault restored
C009 - zone nine reenabled
C006 - high temperature, zone six
C007 - gas detected, zone seven
500
600
DISABLES/
TEST/
BYPASSES
MISC.
System
Test
Sounder/Relay
System Peripheral
Communication
103

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gf510

Table of Contents