Master Programming Level
Freeze Supervision
INPUT ZONE #
1=FREEZE SUPV. NO
2=ACC MSG #
Edit Input Zone Screen #4
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Pressing 1 for Freeze Supv. while viewing Edit Input Zone Screen #4 programs the FACP to supervise the
devices connected to the selected zone for freeze conditions. Each press of the 1 key will toggle the display
between Freeze Supv. Yes and No. The factory default setting is No Freeze Supervision.
Programming
53