General
The GFANN-80 Series Remote Fire Annunciators (GFANN-80,
GFANN-80-W) are compact, backlit LCD displays designed for use
with compatible FACPs (Fire Alarm Control Panels). The displays
mimic the FACP display and are capable of displaying English-language
text of system point status including device type, independent point
alarm, trouble or supervisory zone and custom labels programmed into
the FACP. Refer to the FACP manual installation section for detailed
system information and wiring.
NOTE: Installation and wiring must be done in accordance with
NFPA 72 and local wiring codes.
Specifications
TB1 Terminals 1 & 2
Operating Voltage Range: 18.8VDC to 38.2VDC
Maximum Current Consumption:
Normal/Standby (no activity): 39 mA
Trouble Condition: 46 mA
Alarm: 48 mA
AC Fail (not backlit): 15 mA
TB1 Terminals 3 & 4
ANN-BUS rated at 5.5 VDC and 60 mA max.
Dimensions
6-7/8"W x 5-3/8"H x 1-3/8"D
Mounting
The GFANN-80 Series plastic enclosures can be surface or semi-flush
mounted in a single, double or 4" square electrical box.
To mount the GFANN-80 Series enclosure:
1.
Open the GFANN-80 Series cover by turning the key switch
counterclockwise to the ON (Unlocked) position.
2.
Push in the snap latch tab located on the right side while pulling the
cover open.
3.
Pull wire through 7/8" hole in backplate and feed through wire
channel to lower left corner of backplate before routing to terminal
block (refer to appropriate FACP manual).
Document 53386:B3
4/25/2022
ECN 00016385
Cover with
LCD Display
Figure 1 Opening the GFANN-80 Series
4.
The cover must remain attached to the backplate while mounting
the annunciator to the electrical box/wall. The cover cannot be
reattached or removed after the annunciator has been mounted.
5.
If the cover should become detached from the backplate, reattach as
shown below.
GFANN-80
Series
Cover
Figure 2 Cover Reattachment
6.
Surface or Semi-flush mount the GFANN-80 to a single, double or
4" square electrical box. The ANN-SB80KIT(-R/-B/-W) is an
available kit that contains two plastic backboxes that can be used to
surface mount the GFANN-80 Series.
Backplate
Press in latch
and then
Pull open cover
Key switch shown
in OFF position
• Position cover behind
backplate.
• Align hinge posts and
GFANN-80
holes
Series
• Slide holes down
Backplate
onto posts.
• Close cover to lock
hinges into place.
GFANN-80
GFANN-80
Series
Series
Cover
Backplate

Advertisement

loading

Summary of Contents for Honeywell Gamewell GFANN-80

  • Page 1 GFANN-80 & GFANN-80-W Remote Fire Annunciator Product Installation Document General Backplate The GFANN-80 Series Remote Fire Annunciators (GFANN-80, GFANN-80-W) are compact, backlit LCD displays designed for use with compatible FACPs (Fire Alarm Control Panels). The displays mimic the FACP display and are capable of displaying English-language text of system point status including device type, independent point alarm, trouble or supervisory zone and custom labels programmed into Press in latch...
  • Page 2 Wiring the GFANN-80 Series to the FACP Setting the DIP Switches Refer to Table 1 and Figure 3 for wiring connections. Address Setting  Each ANN-BUS device requires a unique address. DIP switches 1-4 on S1 are used to set the address. This address will be displayed on the GFANN-80 Series FACP ANN-BUS Terminals (TB1)

This manual is also suitable for:

Gamewell gfann-80-w