Honeywell GF505 Manual page 111

Fire alarm control panels
Table of Contents

Advertisement

NFPA 72 Remote Station Protective Signaling System
Notes:
1.
Cut Jumper JP30 on the GF505/GF510 main circuit board to supervise placement of the 4XTMF module.
2.
Refer to"4XTMF Transmitter Module Installation" on page 31 for detailed information.
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.
Figure B.3 Remote Station Connection Using 4XTMF Module
NFPA Standard-Specific Requirements
Polarity Shown is
+
-
Normal Standby
+
Power-limited
-
(Dummy load with a 4.7KΩ, ¼ watt resistor
when no connection is made)
4XTMF Transmitter Module
111