Honeywell GF505 Manual page 74

Fire alarm control panels
Table of Contents

Advertisement

Programming
Event Codes
Pressing 2 while viewing Primary/Secondary Screen #3 will cause the following screen to be displayed:
Pressing the down arrow key allows viewing of all Events associated with the selected Communication Format. Pressing the number cor-
responding to the event displayed in each screen will display its default active and restoral event codes which can be customized by the
programmer.
For example, if Ademco Contact ID is the selected format, pressing 3 for Zone 3 Alarm will display the following screen which allows
the Event Code to be changed from the default value.
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10 and the corresponding Event Codes for
Ademco Contact ID and SIA DCS Formats. Note that Table 3.4 on page 75, Table 3.5 on page 76, Table 3.6 on page 77 and Table 3.7 on
page 79 list the default settings for Zone 1 through Zone 10. These can be changed to any of the Types listed in Table 3.3.
NOTE: The third character in the SIA-DCS Format (x in the table below) represents the zone number.
Pull-Station
Waterflow
Waterflow Nonsilenceable
Combo
Combo AutoResettable Supervisory
2-Wire Detector
Normally Open Contact
Fire
Tamper
Supervisory
Supervisory AutoResettable
Medic-Alert
Hazard-Alert
Tornado-Alert
Proc-Mon
Procmon-AR
AC-Loss-Mon
Drill-Switch
Drill-Switch AutoResettable
The following tables list all of the Events and their default Event Codes for the Ademco Contact ID and SIA-DCS Communication For-
mats.
NOTE: A detector freeze condition will be reported as a Supervisory Event Code.
74
EVENT CODES
1=ZONE 1 ALARM
2=ZONE 2 ALARM
3=ZONE 3 ALARM
ZONE 3 ACTIVE
Zone Alarm Type
Table 3.3 Zone Alarm Type Event Codes
Event Code Screen
115
Ademco Contact ID
Active
115
113
113
113
113
111
110
110
144
200
200
100
150
150
200
200
301
604
604
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Master Programming Level
SIA-DCS Format
Active
Restoral
FAx
FHx
SAx
SHx
SAx
SHx
SAx
SHx
SAx
SHx
FAx
FHx
UAx
UHx
FAx
FHx
TAx
THx
FSx
FVx
FSx
FVx
MAx
MHx
PAx
PHx
PAx
PHx
IAx
IRx
IAx
IRx
ATx
ARx
FIx
FKx
FIx
FKx

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gf510

Table of Contents