LXL-1010 Installation and Setup Guide
Zone Type
Interior Follower
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour Silent
Alarm
Type 07
24-hour Audible
Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Supervised Fire
Type 10
Interior w/Delay
Type 12
Monitor Zone
Type 14
3–4
www.PDF-Zoo.com
Description
through which one must pass upon entry (to and from the keypad).
Provides a delayed alarm (using the programmed entry/exit time) if the
entry/exit zone is faulted first. Otherwise this zone type gives an instant
alarm. Active when the panel is armed in the Away mode.
Bypassed automatically when the panel is armed in the Stay or Instant
modes; if armed in Night-Stay mode, zones assigned to zone list 05
(night-stay zone list) are not bypassed when system armed in Night-Stay
mode.
Assign to a zone that contains a foil-protected door or window (such as in
a store), or to a zone covering a sensitive area such as a stock room, drug
supply room, etc.
Can also be used on a sensor or contact in an area where immediate
notification of an entry is desired.
Provides an instant alarm if faulted when armed in the Away, Stay,
Night-Stay, Instant or Maximum (night) modes.
During the disarmed state (day), the system will provide a latched
trouble sounding from the keypad (and a central station report, if
desired).
Usually assigned to a zone containing an emergency button.
Sends a report to the central station but provides no keypad display or
sounding.
Assign to a zone that has an emergency button.
Sends a report to the central station, and provides an alarm sound at
the keypad, internal sounder, and an audible external alarm.
Assign to a zone containing an emergency button, or to a zone containing
monitoring devices such as water or temperature sensors.
Sends a report to the central station and provides an alarm sound at
the keypad, internal sounder, and an audible external alarm.
Provides a fire alarm when detector is faulted and a trouble condition
when the cover is removed. A fire alarm produces a pulsing internal
sounder output.
This zone type is always active and cannot be bypassed.
Provides entry delay (using the programmed entry time), if tripped when
the panel is armed in the Away mode. Entry Delay 1 timer is
programmable in field *35.
Entry Delay 1 begins whenever sensors in this zone are violated,
regardless of whether or not an entry/exit delay zone was tripped first.
Bypassed when the panel is armed in the Stay or Instant modes; if
armed in Night-Stay mode, zones assigned to zone list 05 (night-stay
zone list) are not bypassed when system armed in Night-Stay mode.
Works as a dynamic monitor of a zone fault/trouble (not alarm). The
system keypad will display a "check" message indicating the appropriate
zone (but keypad beeping does not occur).
The "check" message will automatically disappear from the keypad
dynamically, when the zone restores; a user code + off sequence is not
needed to reset the zone.
Faults of this zone type are independent of the system, and can exist at
the time of arming without interference.
Since this is a "trouble" zone type, do not use this zone type with X-
10 Powerline Carrier Devices set to activate upon "alarm."
Assigned to any zone with a carbon monoxide detector.
firealarmresources.com