Ske-V70 Module Installation; Mounting - Honeywell Silent Knight SKE Series Installation And Operation Manual

Voice evacuation
Table of Contents

Advertisement

Section 8

SKE-V70 Module Installation

The SKE-V70 converts the speaker circuit voltage from 25 Vrms to 70.7 Vrms. The following
sections describe how to install and wire the SKE-V70.
8.1

Mounting

Follow these steps to install the SKE-V70 module into the main control panel cabinet:
1. Unlock and open the cabinet door.
2. Remove the two cover plate retaining screws, then open the control panel cover plate. See
Figure 8-1.
Figure 8-1 View of Cabinet With Cover Plate in Place
Note: The control panel cover plate can be remove by removing the Hinge screw.
3. Run all wire needed to install the system at this time. See Section 8.2.
151267
Control Panel
Cover Plate
Retaining Screws
Hinge Screw
firealarmresources.com
Zone Splitter
Access Plate
Control Panel
Cover Plate
8-1