5.4.4
FACP Alarm Zone Control Wiring
This section describes how to connect relay outputs from a FACP to control the four separate
zones on the SKE-ZN4 four zone splitter.
Connect an active low relay or contact from the FACP to the Alarm Selects on the SKE-ZN4
(see Figure 5-8).
Supervised
Power Limited
151267
Figure 5-8 FACP Alarm Zone Control Outputs
firealarmresources.com
4.7 kΩ
UL Listed EOL
Model 7628
Non-Supervised
Power Limited
Must be wired
within 20 feet
and in conduit.
SKE-ZN4 Zone Splitter
5-9