Section 3

Installation

This section of the manual is intended to help you plan your tasks to facilitate the installation.
Please read this section thoroughly, especially if you are installing a SKE-450 control for the
first time.
3.1

Environmental Specifications

It is important to protect the SKE-450 control panel from moisture. To prevent damage, the
following conditions should be avoided when installing the units:
Mount indoors in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the panel, it should be mounted where it will NOT be
exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity equal to or
greater than 93% at 30°C (89°F) noncondensing.
3.2

Electrical Specification

Circuit
Operating Voltage
Battery Charging Voltage/Circuit
Trouble Relays
Minimum Low AC Detect
* Specify voltage requirements when ordering.
Note: Refer to the control panel wiring diagram to determine which power source is required for your control.
151267
Table 3-1: Electrical Specifications
120 Vrms @ 60 Hz @ 1.2 amp
*230 Vrms @ 50Hz @ .607 amp
27.4 VDC @ 1.9A max/ 0.75 avg
2.5 A @ 30 VDC resistive
92VAC 25V System
94VAC 70.7V System
firealarmresources.com
Rating
3-1